From: Subrahmanya Ramakrishnan Sent: Monday, August 22, 2005 11:35 AM To: Wayne T. Reiersen Subject: FW: C-Site Robicon Supplies Wayne FYI. I have requested Bob Kaita to perform an open-circuit test on the Robicon supplies and advise us the results. Raki -----Original Message----- From: Subrahmanya Ramakrishnan Sent: Thursday, August 18, 2005 10:11 AM To: Ronald E. Hatcher; Charles L. Neumeyer; Alfred von Halle; Robert Kaita Subject: C-Site Robicon Supplies Hi As conveyed, the transformers used in the Robicon supplies are manufactured by NWL. According to the information collected by me following are the published test data on the transformers: Unit Sl# kVA %Z Vp Ip Ip(Pulsed) Vo-sec(No load) T1 86-1258 225 6.07 4160 31.2 125 255 T1 86-1264 225 6.23 4160 31.2 125 255 T2 86-1260 225 5.91 4160 31.2 125 255 T2 86-1262 225 6.12 4160 31.2 125 255 T3 86-1259 225 5.99 4160 31.2 125 255 T3 86-1263 225 5.95 4160 31.2 125 255 T4 86-1261 225 6.25 4160 31.2 125 255 T4 86-1265 225 6.15 4160 31.2 125 255 DF 86-1256 300 6.85 4160 41.7 167 170 DF 86-1257 300 6.92 4160 41.7 167 170 IF 86-1175 1505 5.96 4160 209 836 426 IF 86-1176 1505 5.72 4160 209 836 426 Based on the above information the calculated values of the open circuit voltages do not agree with the values that are used in-house. It is desirable to actually test these voltages on open circuit so that we have proper back up documentation for calculations and simulation that Ron will be providing. The CDX-U will finish operations tomorrow. Bob Kaita has agreed to record the open circuit voltages by energizing the power supplies on Monday August 22nd. Raki