From: Thomas G. Meighan Sent: Thursday, December 15, 2005 3:38 PM To: Wayne T. Reiersen Cc: James H. Chrzanowski Subject: Hipot Test Results of TRC Wayne, The results of the TRC coil are as follows: Ground Wall Test All conductors were at voltage. All Cladding, Chill plates and winding form were grounded. Side "A" Side "B" 5.5 KV Failed 10.5 KV Failed Turn-Turn Results All turns were grounded except the one being tested. Turn Turn "1" Grd. Shorted "1" 7.5KV Failed "2" 5.0 KV Failed "2" Shorted "3" 3.5 KV Failed "3" 6 KV Failed "4" 5.2 KV Failed "4" Shorted when Turn 3 Failed Wayne, If you need any more information please let me know. Tom