I spoke with Bob Parsells regarding occupancy requirements of structures.  Bob, offered an alternative requirement to accommodate people.
You could also size the support per AISC code (24 KSI allowable with an additional reduction of 33% for building safety requirements = 16 KSI) but include a uniform loading of 50 lb. per square foot of area of the vessel. Bob, feel free to correct me if I misunderstood.

Thanks,
Mike Viola, PPPL, (609) 243 3655

On Mar 11, 2008, at 4:30 PM, James H. Chrzanowski wrote:

Tom

Attached FYI is the Design Review results from your PDR on FPA- Station
5.  Included are the Design Review Documentation Results, presentation,
chits and attendance sheet.

Jim<PDR-FPA5 Attendance.pdf><Chit 1.pdf><Chit 2.pdf><Chit 3.pdf><Chit 4.pdf><Chit 5a.pdf><Chit 5b.pdf><PDR FPA Stat5.pdf><NCSX Station 5 PDR.pdf>